新聞中心

MNS低壓抽屜柜的常見故障

發(fā)布時(shí)間:2024-11-12 來源:http://www.digitalsj.cn/ 瀏覽量:

base64_image燒損故障 :

Burn failure:

設(shè)備異常 :開關(guān)跳閘、指示燈熄滅等。

Equipment abnormality: switch tripping, indicator light off, etc.

燃燒現(xiàn)象 :柜內(nèi)出現(xiàn)燃燒,伴隨濃煙和刺鼻氣味。

Burning phenomenon: Burning occurs inside the cabinet, accompanied by thick smoke and a pungent odor.

溫度升高 :柜體溫度異常升高,可能引發(fā)火災(zāi)。

Temperature rise: The cabinet temperature rises abnormally, which may cause a fire.

故障原因 :

Reason for malfunction:

負(fù)載電流超過設(shè)備額定電流,引起設(shè)備過熱。

The load current exceeds the rated current of the equipment, causing overheating of the equipment.

電路短路,產(chǎn)生大量熱量,導(dǎo)致設(shè)備燒損。

A short circuit in the circuit generates a large amount of heat, causing equipment to burn out.

電網(wǎng)電壓波動(dòng)或瞬間高壓可能損壞設(shè)備絕緣。

Voltage fluctuations or momentary high voltage in the power grid may damage equipment insulation.

接觸不良,如抽屜柜內(nèi)部連接點(diǎn)松動(dòng)。

Poor contact, such as loose connection points inside drawer cabinets.

機(jī)械磨損,長時(shí)間運(yùn)行或操作不當(dāng)。

Mechanical wear, prolonged operation or improper handling.

誤操作,如錯(cuò)誤地合閘、分閘。

Incorrect operation, such as closing or opening the circuit incorrectly.

插頭故障 :

Plug malfunction:

一次與二次插頭故障 :主要原因是接觸不良。

Primary and secondary plug faults: The main reason is poor contact.

自動(dòng)開關(guān)無法合閘 :

The automatic switch cannot be closed:

儲(chǔ)能彈簧未儲(chǔ)能 :手動(dòng)合閘過程中,儲(chǔ)能彈簧未完成儲(chǔ)能。

Energy storage spring not stored: During the manual closing process, the energy storage spring did not complete the energy storage.

蘭色按鈕未復(fù)位 :合閘前未將蘭色按鈕復(fù)位。

Blue button not reset: The blue button was not reset before closing.

儲(chǔ)能電機(jī)損壞 :儲(chǔ)能電機(jī)老化或損壞。

Damaged energy storage motor: The energy storage motor is aging or damaged.

控制電源異常 :儲(chǔ)能電機(jī)無法進(jìn)行儲(chǔ)能,接觸不良或控制電路失去。

Abnormal control power supply: The energy storage motor cannot store energy, poor contact or loss of control circuit.

母線故障 :

Bus fault:

母線段進(jìn)線開關(guān)故障 :控制柜內(nèi)K15故障的繼電器動(dòng)作,導(dǎo)致繼電保護(hù)器投入使用。

Bus section incoming switch fault: The relay action of K15 fault in the control cabinet caused the relay protector to be put into use.

抽屜溫度過高 :負(fù)荷過高或接線松動(dòng)引起。

Drawer temperature too high: caused by high load or loose wiring.

斷路器故障 :

Circuit breaker malfunction:

MT10H1型斷路器故障 :瞬時(shí)脫扣lsd系數(shù)設(shè)定值太小,長延時(shí)跳閘延時(shí)tr=4s。

MT10H1 circuit breaker fault: The instantaneous tripping LSD coefficient setting value is too small, and the long delay tripping delay tr=4s.

Emax型斷路器故障 :自動(dòng)空氣開關(guān)跳閘,通常由于母線負(fù)荷超過限定水平或出現(xiàn)相間短路。

Emax type circuit breaker fault: Automatic air switch trips, usually due to bus load exceeding the limit level or phase to phase short circuit.

其他故障 :

Other faults:

負(fù)荷過載 :抽屜開關(guān)下游電氣設(shè)備接地或短路。

Load overload: Electrical equipment downstream of the drawer switch is grounded or short circuited.

熱繼電器故障 :熱繼電器動(dòng)作缺陷。

Thermal relay malfunction: Defects in the operation of the thermal relay.

二次回路端子脫落 :抽屜間隔內(nèi)二次回路端子脫落。

Secondary circuit terminal detachment: The secondary circuit terminal detachment occurs within the drawer compartment.

控制回路電源失去 :220V交流電源或24V直流信號(hào)電源失去。

Control circuit power loss: Loss of 220V AC power or 24V DC signal power.

建議

Suggestion

定期檢查設(shè)備負(fù)載情況,避免過載運(yùn)行。

Regularly check the load condition of the equipment to avoid overload operation.

檢查內(nèi)部連接點(diǎn),確保接觸良好,及時(shí)更換損壞的部件。

Check the internal connection points to ensure good contact and replace damaged components in a timely manner.

加強(qiáng)對設(shè)備的維護(hù)保養(yǎng),定期進(jìn)行電氣設(shè)備的檢查和維護(hù)。

Strengthen the maintenance of equipment and conduct regular inspections and maintenance of electrical equipment.

嚴(yán)格按照操作規(guī)程進(jìn)行操作,避免誤操作導(dǎo)致設(shè)備損壞。

Strictly follow the operating procedures to avoid equipment damage caused by misoperation.

配置合適的保護(hù)裝置,如過載保護(hù)、短路保護(hù)等,確保設(shè)備運(yùn)行。

Configure appropriate protective devices, such as overload protection, short circuit protection, etc., to ensure the safe operation of the equipment.

本文由濟(jì)南MNS低壓抽屜柜為您提供,我們的網(wǎng)站是: http://www.digitalsj.cn 我們將以全心全意的熱情為您提供服務(wù),歡迎您的訪問!

This article is provided by Jinan MNS low-voltage drawer cabinet for you. Our website is: http://www.digitalsj.cn We will provide you with wholehearted enthusiasm and welcome your visit!